Rising Edge Services, LLC

Home Electrical Calculations Contact

Horse Power Calculation, HP

Three Phase HP = (E X I X EFF X PF X 1.732) / 746

Single Phase HP = (E X I X EFF X PF) / 746

Direct Current HP = (E X I X EFF) / 746

Voltage, "E"
Amperes, "I"
Efficiency, "EFF"
Power Factor, "PF"

NOTE: PF and EFF are ignored for the direct current Calculation.

Disclaimer: The information contained on this website is for general information purposes only. Any reliance you place on such information is strictly at your own risk.